Voltage Drop Calculator

Calculate voltage drop and percent drop for copper or aluminum wire in DC, single-phase and three-phase circuits, by AWG or mm².

A
V
°C

Formula used

Formula and method below. Last checked by the SolarCalcLab Editorial Team.

Quick answer

Voltage drop is the voltage lost in a cable’s resistance. For DC and single-phase circuits, Vd = 2 × L × I × R, where L is the one-way length and R is the resistance per meter. For three-phase, Vd = √3 × L × I × R. Divide Vd by the supply voltage for the percentage. The NEC recommends 3% per branch circuit.

SolarCalcLab voltage drop calculator showing 3.64 V with the formula Vd = 2 × 15.24 m × 30 A × 0.003985 Ω/m = 3.644 V
The voltage drop calculator with a worked example. Change any input and the result updates instantly.

How to use the voltage drop calculator

  1. Choose the conductor material. Select copper or aluminum. Aluminum has higher resistance, so it drops more voltage for the same size.
    Step 1: choose the conductor material in the voltage drop calculator
  2. Choose the wire size. Enter the gauge in AWG (for example 10 AWG or 2/0) or the cross-section in mm² (for example 4 mm² or 16 mm²).
    Step 2: choose the wire size in the voltage drop calculator
  3. Enter the one-way length. Measure the cable route from source to load, in feet or meters, including rises and slack. Do not double it.
    Step 3: enter the one-way length in the voltage drop calculator
  4. Enter the current. Use the load current in amps. For solar strings, use the string’s operating current. For battery cables, use the inverter’s maximum DC input current.
    Step 4: enter the current in the voltage drop calculator
  5. Enter the system voltage. Use the nominal voltage at the source, such as 12 V, 24 V or 48 V DC, 120 V or 240 V single-phase, or 208 V, 400 V or 480 V three-phase line-to-line.
    Step 5: enter the system voltage in the voltage drop calculator
  6. Choose the system type. Select DC, single-phase AC or three-phase AC.
    Step 6: choose the system type in the voltage drop calculator
  7. Set the conductor temperature. The default is 75 °C (167 °F). A hotter conductor has higher resistance and more voltage drop.
    Step 7: set the conductor temperature in the voltage drop calculator
  8. Read the result. The calculator shows the voltage drop in volts, the percentage drop and the voltage left at the load.
    Step 8: read the result in the voltage drop calculator

Voltage drop formula

Step 1: Cross-section from AWG

d = 0.127 mm × 92(36 − n) / 39, then A = π × d² / 4

Here n is the AWG number. For 1/0 use n = 0, for 2/0 use n = −1, and so on. If you enter mm², the calculator uses that area directly.

Step 2: Resistance per meter at temperature

R = ρ20 × (1 + α × (T − 20)) / A

Step 3: Voltage drop

DC and single-phase: Vd = 2 × L × I × R
Three-phase: Vd = √3 × L × I × R
Percent drop = Vd / V × 100

Where:

The factor 2 counts the outgoing and return conductors. In a balanced three-phase circuit, the factor √3 (about 1.732) replaces it. The method uses resistance only and ignores reactance, so it is most accurate for DC circuits such as solar strings and battery cables and for smaller AC cables. For large AC feeders, reactance adds some extra drop.

Worked examples

Example 1: 48 V battery cable, 2 AWG copper, 3 m, 100 A

Area: d = 0.127 × 9234/39 = 6.544 mm, so A = 33.63 mm².

R = 0.017241 × (1 + 0.00393 × 55) / 33.63 = 0.017241 × 1.21615 / 33.63 = 0.0006235 Ω/m
Vd = 2 × 3 × 100 × 0.0006235 = 0.374 V (rounded)
Percent = 0.374 / 48 × 100 = 0.78% (rounded)

About 0.37 V is lost between the battery and the inverter, leaving about 47.6 V at full load.

Example 2: 240 V single-phase, 10 AWG copper, 100 ft, 24 A

Length: 100 ft × 0.3048 = 30.48 m. Area: d = 2.588 mm, so A = 5.261 mm².

R = 0.017241 × 1.21615 / 5.261 = 0.003985 Ω/m
Vd = 2 × 30.48 × 24 × 0.003985 = 5.83 V (rounded)
Percent = 5.83 / 240 × 100 = 2.43% (rounded)

The load sees about 234.2 V. This is within the NEC’s 3% branch-circuit recommendation.

Example 3: 400 V three-phase, 4 mm² copper, 50 m, 20 A

R = 0.017241 × 1.21615 / 4 = 0.005242 Ω/m
Vd = 1.732 × 50 × 20 × 0.005242 = 9.08 V (rounded)
Percent = 9.08 / 400 × 100 = 2.27% (rounded)

This is within the BS 7671 guidance of 5% for non-lighting circuits on a public supply.

Voltage drop limits and copper resistance

Recommended and required limits

Rule Applies to Limit Status
NEC 210.19(A) informational note Branch circuit to farthest outlet 3% Recommendation
NEC 210.19(A) and 215.2(A) informational notes Feeder plus branch circuit combined 5% Recommendation
NEC 647.4(D) Sensitive electronic equipment: branch circuit / feeder plus branch 1.5% / 2.5% Requirement
BS 7671 Appendix 4 (public LV supply) Lighting 3% Guidance
BS 7671 Appendix 4 (public LV supply) Other uses 5% Guidance

Copper resistance at 75 °C

Computed with the method above (ρ20 = 0.017241 Ω·mm²/m, α = 0.00393 per °C). Values are per single conductor and rounded.

Size Area (mm²) Ω per 1,000 ft Ω per km
14 AWG 2.08 3.071 10.08
12 AWG 3.31 1.932 6.337
10 AWG 5.26 1.215 3.985
8 AWG 8.37 0.764 2.506
6 AWG 13.30 0.480 1.576
4 AWG 21.15 0.302 0.991
2 AWG 33.63 0.190 0.623
1/0 AWG 53.48 0.119 0.392
2/0 AWG 67.43 0.095 0.311
2.5 mm² 2.5 2.556 8.387
4 mm² 4 1.598 5.242
6 mm² 6 1.065 3.495
10 mm² 10 0.639 2.097
16 mm² 16 0.399 1.310
25 mm² 25 0.256 0.839
35 mm² 35 0.183 0.599

For aluminum at the same size and temperature, resistance is about 1.65 times the copper value.

What affects the result

Cable length

Voltage drop rises in direct proportion to length. Doubling the run from 50 ft to 100 ft doubles the drop.

Wire size

Resistance falls as the cross-section grows. Each step of three AWG sizes roughly halves the area and doubles the resistance. Going from 10 AWG to 8 AWG cuts the drop by about 37%.

Current and system voltage

Drop in volts rises with current. The percentage drop also depends on the system voltage, so low-voltage DC systems are most sensitive. A 1 V loss is about 8% of a 12 V system but under 1% of a 240 V circuit. This is a main reason solar battery banks move from 12 V to 24 V or 48 V as they grow.

Conductor temperature

Copper resistance rises about 0.39% per °C. At 75 °C, copper has about 22% more resistance than at 20 °C. Hot attics, rooftop conduit and fully loaded cables run warmer, so a 20 °C figure understates the real drop.

Frequently asked questions

What is an acceptable voltage drop?

In the US, NEC informational notes recommend no more than 3% on a branch circuit and 5% for the feeder and branch circuit combined. In the UK, BS 7671 Appendix 4 gives 3% for lighting and 5% for other uses on installations fed from the public low-voltage supply. Lower is better for efficiency.

Is the NEC 3% rule mandatory?

In most cases, no. The 3% and 5% figures appear in informational notes, which are advisory. The NEC does make voltage drop mandatory in a few places, such as Article 647 for sensitive electronic equipment, which limits branch circuits to 1.5% and feeder plus branch to 2.5%. Local rules or designers may set stricter limits.

Should I enter the one-way or round-trip length?

Enter the one-way length from the source to the load. The calculator multiplies by 2 for DC and single-phase circuits to include the return conductor, and by √3 for three-phase circuits. Entering the round-trip length by mistake would double the calculated result.

Why use 75 °C for conductor temperature?

Conductors carrying load run warmer than room temperature, and resistance rises with heat. A 75 °C default matches a common conductor temperature rating and gives a conservative result. If you know the cable runs cooler, lower the temperature and the calculated drop will fall slightly.

Does this work for solar panel strings?

Yes. Choose DC, enter the string’s operating current and voltage, and the one-way distance from the array to the inverter or charge controller. Because the method ignores reactance, it is well suited to DC solar wiring, charge controller runs and battery cables.

Related calculators