Wire Size Calculator

Find the minimum copper or aluminum wire gauge that meets both NEC ampacity and your voltage drop limit, in AWG and mm².

Conductor material
A
Use the full-load current. For solar PV source circuits, enter Isc × 1.25 and mark the load as continuous.
The NEC sizes conductors for continuous loads at 125% of the load current.
V
Voltage drop limit

Formula used

Formula and method below. Last checked by the SolarCalcLab Editorial Team.

Quick answer

The right wire size is the smallest conductor passing two checks: its NEC Table 310.16 ampacity covers the load, and its voltage drop stays under your limit. Voltage drop is Vd = 2 × L × I × R for single-phase and DC. A 30 A, 240 V load 100 ft away needs 8 AWG copper for a 3% limit.

SolarCalcLab wire size calculator showing 8 AWG for the default example
The Wire Size calculator with a worked example. Change any input and the result updates instantly.

How to use the wire size calculator

  1. Choose the conductor material. Pick copper for most branch circuits and DC battery cables. Pick aluminum for larger feeders and service conductors.
    Step 1: choose the conductor material in the Wire Size calculator
  2. Enter the load current. Use the nameplate full-load amps or watts ÷ volts. For a solar PV source circuit, enter the module Isc × 1.25.
    Step 2: enter the load current in the Wire Size calculator
  3. Choose the load type. Pick continuous if the maximum current runs for 3 hours or more, such as EV charging, heaters or solar circuits. The calculator then sizes for 125% of the current.
    Step 3: choose the load type in the Wire Size calculator
  4. Enter the system voltage. Use the circuit voltage, such as 120 V, 240 V, or 12 V, 24 V or 48 V for battery systems. For three-phase, use the line-to-line voltage.
    Step 4: enter the system voltage in the Wire Size calculator
  5. Choose the system type. DC and single-phase AC use a factor of 2 for the out-and-back path. Three-phase AC uses √3.
    Step 5: choose the system type in the Wire Size calculator
  6. Enter the one-way length. Measure the cable route from source to load in feet or meters.
    Step 6: enter the one-way length in the Wire Size calculator
  7. Pick the voltage drop limit. 3% is a common target for a branch circuit or feeder. Use 2% for low-voltage DC runs and 5% only where more drop is acceptable.
    Step 7: pick the voltage drop limit in the Wire Size calculator
  8. Read the minimum wire size. The big result is the smallest AWG or kcmil size that passes both checks. The line below it tells you whether ampacity or voltage drop decided the size.
    Step 8: read the minimum wire size in the Wire Size calculator

Wire size formula

The calculator runs two tests and takes the larger of the two sizes.

1. Ampacity check

Itable ≥ I × 1.25 (continuous) or I × 1 (non-continuous)

Itable is the 75 °C ampacity from NEC Table 310.16, capped for 14, 12 and 10 AWG by the small-conductor limits in NEC 240.4(D).

2. Voltage drop check

Vd = k × L × I × ρ20 × (1 + α(75 − 20)) ÷ A
Vd% = Vd ÷ V × 100 ≤ limit

Where:

Worked examples

Example 1: 30 A at 240 V over 100 ft, copper

Ampacity alone allows 10 AWG: Table 310.16 lists 35 A, and 240.4(D) caps it at 30 A, which still covers 30 A. Now check the drop. 100 ft is 30.48 m and copper at 75 °C has ρ = 0.02097 Ω·mm²/m.

10 AWG: Vd = 2 × 30.48 × 30 × 0.02097 ÷ 5.26 = 7.29 V = 3.04%
8 AWG: Vd = 2 × 30.48 × 30 × 0.02097 ÷ 8.37 = 4.58 V = 1.91%

10 AWG misses the 3% limit, so voltage drop governs and the answer is 8 AWG copper.

Example 2: 100 A aluminum feeder at 240 V, 150 ft

Aluminum 1 AWG has a 75 °C ampacity of 100 A, so it passes the ampacity test. At 150 ft (45.72 m), aluminum at 75 °C has ρ = 0.03453 Ω·mm²/m.

1 AWG: Vd = 2 × 45.72 × 100 × 0.03453 ÷ 42.41 = 7.45 V = 3.10%
1/0 AWG: Vd = 2 × 45.72 × 100 × 0.03453 ÷ 53.48 = 5.90 V = 2.46%

The result is 1/0 AWG aluminum. If the same feeder were a continuous load, the 125 A requirement would push ampacity to 2/0 AWG (135 A).

Example 3: 20 A at 12 V DC over 15 ft

12 AWG copper covers 20 A. But at 12 V, a 3% drop is only 0.36 V. With 15 ft = 4.57 m:

8 AWG: Vd = 2 × 4.57 × 20 × 0.02097 ÷ 8.37 = 0.46 V = 3.82%
6 AWG: Vd = 2 × 4.57 × 20 × 0.02097 ÷ 13.30 = 0.29 V = 2.40%

Here voltage drop governs and the answer is 6 AWG.

Wire ampacity chart (NEC Table 310.16, 75 °C)

Values are for not more than three current-carrying conductors in a raceway or cable at 30 °C (86 °F) ambient. Where 240.4(D) applies, the overcurrent limit is shown in brackets.

Size Area (mm²) Copper 75 °C Aluminum 75 °C
14 AWG 2.08 20 A [15 A] not listed
12 AWG 3.31 25 A [20 A] 20 A [15 A]
10 AWG 5.26 35 A [30 A] 30 A [25 A]
8 AWG 8.37 50 A 40 A
6 AWG 13.30 65 A 50 A
4 AWG 21.15 85 A 65 A
2 AWG 33.63 115 A 90 A
1/0 AWG 53.48 150 A 120 A
2/0 AWG 67.43 175 A 135 A
4/0 AWG 107.22 230 A 180 A
250 kcmil 126.7 255 A 205 A
500 kcmil 253.4 380 A 310 A

The calculator also uses 3, 1, 3/0, 300, 350 and 400 sizes. Always confirm against the edition of the National Electrical Code (NFPA 70) your area has adopted.

What affects the result

Terminal temperature rating

The 75 °C column only applies when every termination on the circuit is rated for 75 °C. For circuits of 100 A or less, NEC 110.14(C) uses the 60 °C column unless the equipment is listed for 75 °C, which lowers the usable ampacity. Check the breaker and equipment labels.

Ambient temperature and bundling

Table 310.16 assumes 30 °C ambient and no more than three current-carrying conductors together. Hot attics, rooftop conduit in sun and more conductors in one raceway all need correction factors, which can call for a larger size. The 75 °C column covers types such as THWN, XHHW and USE; other insulation types differ.

Run length and voltage

Voltage drop rises with length and current. Doubling the voltage cuts the percentage drop to one quarter for the same power, so long runs and low-voltage DC circuits are usually sized by voltage drop.

Local code and conduit fill

Your local authority may adopt a different NEC edition or add rules, and the conduit must have room for the conductors. Treat the result as a starting size, not a permit design.

Frequently asked questions

What size wire do I need for 30 amps?

For copper with 75 °C terminals, 10 AWG covers 30 A on ampacity and the 240.4(D) limit. On longer runs, voltage drop can push it to 8 AWG. A 30 A load at 240 V over 100 ft needs 8 AWG to stay under 3%. Aluminum needs at least 8 AWG for 30 A.

What is the difference between AWG and mm²?

AWG is the American Wire Gauge scale, where a smaller number means a thicker wire. Metric sizes give the cross-section directly in square millimeters. 10 AWG is about 5.26 mm² and 4 AWG is about 21.15 mm². Metric cables are rated under IEC rules, not the NEC table.

Why does voltage drop matter?

Every wire has resistance, so some voltage is lost along the run. Too much drop makes motors run hot and lights dim, and it wastes energy as heat. Keeping the drop near 3% for a branch circuit or feeder is a widely used design target.

Can I use aluminum wire instead of copper?

Yes, for many feeders and service conductors, provided the terminals are rated for aluminum. Aluminum has higher resistance, so it needs a larger size for the same current. The NEC table does not list 14 AWG aluminum, and small aluminum branch circuits are uncommon today.

What does continuous load mean?

The NEC treats a load as continuous when the maximum current is expected to last 3 hours or more. Conductors for continuous loads are sized at 125% of the current. EV chargers, electric heat and solar PV circuits are typical examples, so a 32 A charger needs 40 A of ampacity.