Radiator Output Calculator

Convert a radiator's ΔT50 rating to its real heat output at any flow, return and room temperature, using the EN 442 method.

The catalog output at ΔT50 (75/65°C flow and return in a 20°C room), per EN 442.
°C
°C
Heat pumps usually run 5°C below flow. Boilers run 10 to 20°C below.
°C
1.3 is the standard value for panel radiators. Check the datasheet for towel rails and column radiators.

Formula used

Formula and method below. Last checked by the SolarCalcLab Editorial Team.

Quick answer

A radiator’s actual output is its ΔT50 rating multiplied by (ΔT ÷ 50)1.3, where ΔT is the mean water temperature minus the room temperature. A 1,500 W radiator on a heat pump at 50°C flow and 45°C return in a 21°C room has a ΔT of 26.5°C, so it gives 1,500 × 0.438 = 657 W, or 43.8% of its rating. On a boiler at 75/65°C in a 20°C room it gives the full 1,500 W.

SolarCalcLab Radiator Output calculator showing 657 W for the default example
The Radiator Output calculator with a worked example. Change any input and the result updates instantly.

How to use the radiator output calculator

  1. Enter the rated output at ΔT50. Type the figure from the manufacturer’s catalog or datasheet and choose W or BTU/h. UK catalogs quote outputs at ΔT50 to EN 442.
    Step 1: enter the rated output at Δt50 in the Radiator Output calculator
  2. Enter the flow and return temperatures. Flow is the water temperature entering the radiator and return is the temperature leaving it. Heat pumps typically run 5°C between the two, and boilers 10 to 20°C.
    Step 2: enter the flow and return temperatures in the Radiator Output calculator
  3. Enter the room temperature. Use the temperature you want the room to reach, such as 21°C for a living room or 18°C for a bedroom.
    Step 3: enter the room temperature in the Radiator Output calculator
  4. Check the exponent. Leave n at 1.3 for standard steel panel radiators. Some column radiators and towel rails list a different value on their datasheet.
    Step 4: check the exponent in the Radiator Output calculator
  5. Read the actual output. The large number is the real heat output at your temperatures. The cards show the ΔT, the correction factor and the ΔT50 rating you would need to get the original output at these temperatures.
    Step 5: read the actual output in the Radiator Output calculator

Radiator output formula

Radiator output rises faster than the temperature difference, because hotter surfaces also lose more heat by convection. EN 442 describes this with a power law.

ΔT = (Tflow + Treturn) ÷ 2 − Troom
F = (ΔT ÷ 50)n
Q = Q50 × F

Where:

To go the other way, divide the heat you need by F. That is how the calculator finds the ΔT50 rating needed at low temperatures. Zehnder’s correction factor guide uses the same arithmetic mean and n = 1.3.

Worked examples

Example 1: heat pump at 50/45°C

The default. A 1,500 W radiator, 50°C flow, 45°C return, 21°C room. The mean water temperature is 47.5°C, so ΔT = 26.5°C.

Q = 1,500 × (26.5 ÷ 50)1.3 = 1,500 × 0.4381 = 657 W

To get the full 1,500 W at these temperatures you would need a radiator rated about 3,424 W at ΔT50.

Example 2: condensing boiler at 70/50°C

A 1,000 W radiator on a condensing boiler set to 70°C flow with a 20°C drop, in a 20°C room. ΔT = 60 − 20 = 40°C.

Q = 1,000 × (40 ÷ 50)1.3 = 1,000 × 0.748 = 748 W

The lower return temperature helps the boiler condense and run more efficiently, but the radiator gives 25% less heat.

Example 3: heat pump at 55/50°C

A 1,200 W radiator in a 20°C room, with 55°C flow and 50°C return. ΔT = 52.5 − 20 = 32.5°C.

Q = 1,200 × (32.5 ÷ 50)1.3 = 1,200 × 0.5712 = 685 W

Raising the flow temperature by 5°C over Example 1 adds output but lowers the heat pump’s efficiency, so larger radiators are usually the better fix.

Radiator correction factor table (n = 1.3)

Output of a radiator rated 1,000 W at ΔT50, and the multiplier to apply to the heat you need to find the ΔT50 rating to buy.

Flow / return / room (°C) ΔT Correction factor Output of a 1,000 W radiator Oversize factor
75 / 65 / 20 50 1.000 1,000 W 1.00
70 / 60 / 20 45 0.872 872 W 1.15
70 / 50 / 20 40 0.748 748 W 1.34
60 / 50 / 20 35 0.629 629 W 1.59
55 / 45 / 20 30 0.515 515 W 1.94
55 / 50 / 21 31.5 0.548 548 W 1.82
50 / 45 / 21 26.5 0.438 438 W 2.28
45 / 40 / 21 21.5 0.334 334 W 3.00
40 / 35 / 21 16.5 0.237 237 W 4.23
35 / 30 / 21 11.5 0.148 148 W 6.76

Manufacturers’ printed tables can differ in the third decimal place because some use a slightly different exponent for each model.

What affects the result

Flow temperature

Flow temperature has the biggest effect. Every 5°C drop in mean water temperature near ΔT30 cuts output by roughly a fifth. That is why a heat pump designer either keeps the flow temperature low and fits larger radiators, or accepts a lower efficiency at a higher flow temperature. The heat pump running cost calculator shows what that efficiency difference costs.

Room temperature

The same water temperature gives more heat in a cooler room. A radiator at 50/45°C gives 438 W per 1,000 W rated in a 21°C living room, but about 504 W in an 18°C bedroom (ΔT 29.5°C).

Arithmetic or log mean ΔT

UK makers use the simple average of flow and return. The more exact log mean temperature difference is slightly lower when the drop across the radiator is large. At 50/45°C in a 21°C room the log mean is 26.4°C against 26.5°C, so the difference is negligible for heat pumps.

Radiator type and installation

The exponent n varies from about 1.25 to 1.35 between panel, column and fan-assisted designs. Covers, shelves, curtains and painting with metallic paints all reduce output. To size radiators from scratch, use the radiator size calculator.

Frequently asked questions

What is delta T on a radiator?

Delta T (ΔT) is the difference between the radiator’s mean water temperature and the room air temperature. The mean is the average of the flow and return temperatures. A radiator at 75°C flow and 65°C return has a 70°C mean, so in a 20°C room ΔT is 50°C, the standard rating condition.

How do I convert ΔT50 to ΔT30?

Multiply the ΔT50 output by (30 ÷ 50)1.3, which is 0.515. A 2,000 W radiator at ΔT50 gives about 1,030 W at ΔT30. To find the rating you need, divide the room’s heat loss by 0.515, which is the same as multiplying it by 1.94.

Why does my radiator give less heat with a heat pump?

A heat pump heats water to around 45 to 55°C instead of 70 to 75°C from a gas boiler. A smaller temperature difference between the water and the room means less heat flows out, and the 1.3 exponent makes the drop steeper. At 50/45°C a radiator gives under half its rating.

What is the EN 442 radiator exponent?

EN 442 is the European standard for testing radiators. Each model is tested at several temperatures and the results are fitted to the equation Q = K × ΔTn. For most steel panel radiators n is close to 1.3, which is the value this calculator uses by default.

Can a radiator work at ΔT20?

Yes, but it gives only about 30% of its ΔT50 rating. Low ΔT operation suits underfloor heating or very well insulated homes with large radiators. In a typical UK home, running at ΔT20 usually means two or three times the radiator area, or fan-assisted radiators.