Wire Gauge Amp Chart: AWG Ampacity for Copper and Aluminum

Copper wire cross-sections for 14, 10, 6 and 2 AWG with their ampacity of 15, 30, 65 and 115 amps

Short answer

For copper building wire, 14 AWG is limited to a 15 A breaker, 12 AWG to 20 A and 10 AWG to 30 A. Beyond that, read NEC Table 310.16: at the 75°C column, 8 AWG carries 50 A, 6 AWG 65 A, 4 AWG 85 A, 2 AWG 115 A and 1/0 AWG 150 A. Aluminum needs roughly two sizes larger for the same current.

A wire gauge amp chart answers one question: how much current a conductor can carry before its insulation gets too hot. It does not tell you how far you can run that wire, what happens in a hot attic, or which breaker the code allows on it. Those are the three things that usually change the answer, so this page puts the chart first and then walks through each one with real numbers.

The values below come from Table 310.16 of NFPA 70, the National Electrical Code. They assume an ambient temperature of 86°F (30°C) and no more than three current-carrying conductors in a cable or raceway.

AWG ampacity chart: copper and aluminum

Wire size Copper 60°C Copper 75°C Copper 90°C Aluminum 75°C
14 AWG 15 A 20 A* 25 A* n/a
12 AWG 20 A 25 A* 30 A* 20 A*
10 AWG 30 A 35 A* 40 A* 30 A*
8 AWG 40 A 50 A 55 A 40 A
6 AWG 55 A 65 A 75 A 50 A
4 AWG 70 A 85 A 95 A 65 A
3 AWG 85 A 100 A 115 A 75 A
2 AWG 95 A 115 A 130 A 90 A
1 AWG 110 A 130 A 145 A 100 A
1/0 AWG 125 A 150 A 170 A 120 A
2/0 AWG 145 A 175 A 195 A 135 A
3/0 AWG 165 A 200 A 225 A 155 A
4/0 AWG 195 A 230 A 260 A 180 A
250 kcmil 215 A 255 A 290 A 205 A
350 kcmil 260 A 310 A 350 A 250 A
500 kcmil 320 A 380 A 430 A 310 A

*Section 240.4(D) caps the overcurrent device on small conductors no matter what the column says: 15 A for 14 AWG copper, 20 A for 12 AWG copper, 30 A for 10 AWG copper, 15 A for 12 AWG aluminum and 25 A for 10 AWG aluminum. The higher figures are still useful as a starting point when you derate, which is covered below.

Bar chart of copper wire ampacity at the 75°C column: 14 AWG 20 A with a 15 A breaker limit, 12 AWG 25 A with a 20 A limit, 10 AWG 35 A with a 30 A limit, 8 AWG 50 A, 6 AWG 65 A, 4 AWG 85 A, 2 AWG 115 A, 1/0 AWG 150 A
Copper ampacity at the 75°C column of NEC Table 310.16. For 14, 12 and 10 AWG the breaker limit in Section 240.4(D) is lower than the table value.

Which column applies to your wire

The three copper columns describe insulation temperature ratings, but a circuit is only as good as its weakest part. In most homes that part is the breaker or lug, not the wire.

  • NM cable (Romex): always the 60°C column, under Section 334.80, even though the conductors inside are rated 90°C.
  • THHN or THWN-2 in conduit, 100 A or less: the 60°C column by default. You may use 75°C when both ends terminate on equipment marked 75°C, which most modern breakers and panels are.
  • Above 100 A, or wire larger than 1 AWG: the 75°C column.
  • The 90°C column: only a starting number for derating. The final result still cannot exceed the termination rating.

Wire size by breaker

Most people come to a chart like this with a breaker size already in mind. This table gives the smallest wire for each common breaker, split by the column that applies.

Breaker Copper, 60°C (NM cable) Copper, 75°C terminals Aluminum, 75°C
15 A 14 AWG 14 AWG 12 AWG
20 A 12 AWG 12 AWG 10 AWG
30 A 10 AWG 10 AWG 8 AWG
40 A 8 AWG 8 AWG 8 AWG
50 A 6 AWG 8 AWG 6 AWG
60 A 4 AWG 6 AWG 4 AWG
70 A 4 AWG 4 AWG 3 AWG
100 A 1 AWG 3 AWG 1 AWG

Each gauge has its own detailed guide with uses, wattage limits and run lengths: 14 gauge, 12 gauge, 10 gauge, 8 gauge, 6 AWG and 4 gauge. For a breaker-first walk-through, see what size wire for a 40 amp breaker.

Continuous loads change the math

A load that runs three hours or more, such as an EV charger, a water heater or a solar inverter output, is sized at 125% of its current. A 32 A EV charger needs a circuit and wire good for 40 A. A 48 A charger needs 60 A, which puts it on 6 AWG copper with 75°C terminals. Divide watts by volts first if you only know the wattage. The watts to amps calculator does that step.

Derating: when the chart number drops

Heat is the enemy. Two conditions reduce a conductor’s allowed current: a hotter room than 86°F, and more than three current-carrying wires packed together. The factors multiply.

Condition Factor (90°C wire) Factor (75°C wire)
Ambient 88 to 95°F (31 to 35°C) 0.96 0.94
Ambient 97 to 104°F (36 to 40°C) 0.91 0.88
Ambient 106 to 113°F (41 to 45°C) 0.87 0.82
4 to 6 current-carrying conductors 0.80 0.80
7 to 9 current-carrying conductors 0.70 0.70
Derated ampacity = 90°C table value × temperature factor × bundling factor

Example 1: two 20 A circuits in one conduit through an attic

Six 12 AWG THHN conductors share a conduit in an attic that reaches 104°F. Start from the 90°C value of 30 A: 30 × 0.91 × 0.80 = 21.8 A. That is still above 20 A, so 12 AWG on 20 A breakers is fine.

Example 2: three 30 A circuits in a hot garage

Nine 10 AWG THHN conductors run through a garage that hits 110°F. Start from 40 A: 40 × 0.87 × 0.70 = 24.4 A. That is below 30 A, so you need 8 AWG, or two conduits. This is where people get caught, because the wire looks correct on the plain chart.

Voltage drop: ampacity is not the whole answer

Ampacity keeps wire from overheating. It says nothing about the voltage lost along the run, and on long branch circuits and low-voltage DC systems, voltage drop usually decides the gauge.

Max one-way length (ft) = allowed drop in volts ÷ (2 × amps × ohms per foot)
12 AWG copper, 20 A at 120 V, 3% drop: 3.6 ÷ (2 × 20 × 0.00193) = 46.6 ft

So a 20 A circuit at full load on 12 AWG stays within 3% for about 47 feet. At a 16 A continuous load the limit rises to about 58 feet. Past that, step up to 10 AWG, or check your exact load in the voltage drop calculator.

12 V DC: the chart can mislead badly

At 12 V, a 3% drop is only 0.36 V. Using copper resistance from NEC Chapter 9, Table 8, here is the longest one-way run each gauge allows:

Gauge 10 A load 20 A load 50 A load
12 AWG 9.3 ft 4.7 ft 1.9 ft
10 AWG 14.9 ft 7.4 ft 3.0 ft
8 AWG 23.6 ft 11.8 ft 4.7 ft
6 AWG 36.7 ft 18.3 ft 7.3 ft
4 AWG 58.4 ft 29.2 ft 11.7 ft
2 AWG 92.8 ft 46.4 ft 18.6 ft
1/0 AWG 147.5 ft 73.8 ft 29.5 ft

A 12 V fridge drawing 10 A, 15 feet from the battery, needs 8 AWG even though 14 AWG has the ampacity. That is why RV and van wiring often looks oversized next to house wiring. For solar arrays, the solar cable size calculator applies the same check with PV-specific current rules.

Copper or aluminum?

The last column of the main chart shows the trade. Aluminum carries roughly 78 to 80% as much current as copper of the same size, so a 100 A feeder needs 1 AWG aluminum instead of 3 AWG copper. In exchange it costs much less per foot at large sizes and weighs less. Aluminum makes sense for feeders, service entrance cable and long runs to outbuildings. Copper is the norm for branch circuits of 30 A and below. Our aluminum wire ampacity chart covers every aluminum size, the 83% dwelling service rule and termination practice.

When a job has several variables at once, such as distance, load, temperature and material, the wire size calculator checks ampacity and voltage drop together and returns the larger of the two answers.

Frequently asked questions

What gauge wire do I need for 20 amps?

12 AWG copper is the minimum for a 20 A circuit, including 12/2 NM cable. Use 10 AWG if the run is long enough to push voltage drop past 3%, which for a fully loaded 120 V circuit starts at roughly 47 feet one way.

Does a wire gauge amp chart apply to DC wiring?

Yes for heating, since a conductor warms the same way with AC or DC current. But in 12 V and 24 V systems, voltage drop almost always forces a larger wire than the ampacity chart suggests, so size low-voltage DC runs by distance first.

Why do some charts show much higher amps for the same gauge?

Charts labeled “chassis wiring” or “free air” describe single wires inside equipment with open air around them. They are not for building wire in walls, cables or conduit. For house wiring, use NEC Table 310.16 values.

How much bigger is each step in wire gauge?

Each AWG step changes cross-sectional area by about 26%, so every three gauge numbers the area roughly doubles and resistance halves. That is why going from 12 to 10 AWG cuts voltage drop by a bit more than a third.

Can I use the 90°C column for THHN wire?

Only as the starting point for derating. Breakers and panel lugs are usually rated 60°C or 75°C, and the circuit is limited by the lowest rating, so the final ampacity you use must come from that column.