Wire Gauge Amp Chart: AWG Ampacity for Copper and Aluminum

Short answer
For copper building wire, 14 AWG is limited to a 15 A breaker, 12 AWG to 20 A and 10 AWG to 30 A. Beyond that, read NEC Table 310.16: at the 75°C column, 8 AWG carries 50 A, 6 AWG 65 A, 4 AWG 85 A, 2 AWG 115 A and 1/0 AWG 150 A. Aluminum needs roughly two sizes larger for the same current.
A wire gauge amp chart answers one question: how much current a conductor can carry before its insulation gets too hot. It does not tell you how far you can run that wire, what happens in a hot attic, or which breaker the code allows on it. Those are the three things that usually change the answer, so this page puts the chart first and then walks through each one with real numbers.
The values below come from Table 310.16 of NFPA 70, the National Electrical Code. They assume an ambient temperature of 86°F (30°C) and no more than three current-carrying conductors in a cable or raceway.
AWG ampacity chart: copper and aluminum
| Wire size | Copper 60°C | Copper 75°C | Copper 90°C | Aluminum 75°C |
|---|---|---|---|---|
| 14 AWG | 15 A | 20 A* | 25 A* | n/a |
| 12 AWG | 20 A | 25 A* | 30 A* | 20 A* |
| 10 AWG | 30 A | 35 A* | 40 A* | 30 A* |
| 8 AWG | 40 A | 50 A | 55 A | 40 A |
| 6 AWG | 55 A | 65 A | 75 A | 50 A |
| 4 AWG | 70 A | 85 A | 95 A | 65 A |
| 3 AWG | 85 A | 100 A | 115 A | 75 A |
| 2 AWG | 95 A | 115 A | 130 A | 90 A |
| 1 AWG | 110 A | 130 A | 145 A | 100 A |
| 1/0 AWG | 125 A | 150 A | 170 A | 120 A |
| 2/0 AWG | 145 A | 175 A | 195 A | 135 A |
| 3/0 AWG | 165 A | 200 A | 225 A | 155 A |
| 4/0 AWG | 195 A | 230 A | 260 A | 180 A |
| 250 kcmil | 215 A | 255 A | 290 A | 205 A |
| 350 kcmil | 260 A | 310 A | 350 A | 250 A |
| 500 kcmil | 320 A | 380 A | 430 A | 310 A |
*Section 240.4(D) caps the overcurrent device on small conductors no matter what the column says: 15 A for 14 AWG copper, 20 A for 12 AWG copper, 30 A for 10 AWG copper, 15 A for 12 AWG aluminum and 25 A for 10 AWG aluminum. The higher figures are still useful as a starting point when you derate, which is covered below.

Which column applies to your wire
The three copper columns describe insulation temperature ratings, but a circuit is only as good as its weakest part. In most homes that part is the breaker or lug, not the wire.
- NM cable (Romex): always the 60°C column, under Section 334.80, even though the conductors inside are rated 90°C.
- THHN or THWN-2 in conduit, 100 A or less: the 60°C column by default. You may use 75°C when both ends terminate on equipment marked 75°C, which most modern breakers and panels are.
- Above 100 A, or wire larger than 1 AWG: the 75°C column.
- The 90°C column: only a starting number for derating. The final result still cannot exceed the termination rating.
Wire size by breaker
Most people come to a chart like this with a breaker size already in mind. This table gives the smallest wire for each common breaker, split by the column that applies.
| Breaker | Copper, 60°C (NM cable) | Copper, 75°C terminals | Aluminum, 75°C |
|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 12 AWG | 10 AWG |
| 30 A | 10 AWG | 10 AWG | 8 AWG |
| 40 A | 8 AWG | 8 AWG | 8 AWG |
| 50 A | 6 AWG | 8 AWG | 6 AWG |
| 60 A | 4 AWG | 6 AWG | 4 AWG |
| 70 A | 4 AWG | 4 AWG | 3 AWG |
| 100 A | 1 AWG | 3 AWG | 1 AWG |
Each gauge has its own detailed guide with uses, wattage limits and run lengths: 14 gauge, 12 gauge, 10 gauge, 8 gauge, 6 AWG and 4 gauge. For a breaker-first walk-through, see what size wire for a 40 amp breaker.
Continuous loads change the math
A load that runs three hours or more, such as an EV charger, a water heater or a solar inverter output, is sized at 125% of its current. A 32 A EV charger needs a circuit and wire good for 40 A. A 48 A charger needs 60 A, which puts it on 6 AWG copper with 75°C terminals. Divide watts by volts first if you only know the wattage. The watts to amps calculator does that step.
Derating: when the chart number drops
Heat is the enemy. Two conditions reduce a conductor’s allowed current: a hotter room than 86°F, and more than three current-carrying wires packed together. The factors multiply.
| Condition | Factor (90°C wire) | Factor (75°C wire) |
|---|---|---|
| Ambient 88 to 95°F (31 to 35°C) | 0.96 | 0.94 |
| Ambient 97 to 104°F (36 to 40°C) | 0.91 | 0.88 |
| Ambient 106 to 113°F (41 to 45°C) | 0.87 | 0.82 |
| 4 to 6 current-carrying conductors | 0.80 | 0.80 |
| 7 to 9 current-carrying conductors | 0.70 | 0.70 |
Example 1: two 20 A circuits in one conduit through an attic
Six 12 AWG THHN conductors share a conduit in an attic that reaches 104°F. Start from the 90°C value of 30 A: 30 × 0.91 × 0.80 = 21.8 A. That is still above 20 A, so 12 AWG on 20 A breakers is fine.
Example 2: three 30 A circuits in a hot garage
Nine 10 AWG THHN conductors run through a garage that hits 110°F. Start from 40 A: 40 × 0.87 × 0.70 = 24.4 A. That is below 30 A, so you need 8 AWG, or two conduits. This is where people get caught, because the wire looks correct on the plain chart.
Voltage drop: ampacity is not the whole answer
Ampacity keeps wire from overheating. It says nothing about the voltage lost along the run, and on long branch circuits and low-voltage DC systems, voltage drop usually decides the gauge.
12 AWG copper, 20 A at 120 V, 3% drop: 3.6 ÷ (2 × 20 × 0.00193) = 46.6 ft
So a 20 A circuit at full load on 12 AWG stays within 3% for about 47 feet. At a 16 A continuous load the limit rises to about 58 feet. Past that, step up to 10 AWG, or check your exact load in the voltage drop calculator.
12 V DC: the chart can mislead badly
At 12 V, a 3% drop is only 0.36 V. Using copper resistance from NEC Chapter 9, Table 8, here is the longest one-way run each gauge allows:
| Gauge | 10 A load | 20 A load | 50 A load |
|---|---|---|---|
| 12 AWG | 9.3 ft | 4.7 ft | 1.9 ft |
| 10 AWG | 14.9 ft | 7.4 ft | 3.0 ft |
| 8 AWG | 23.6 ft | 11.8 ft | 4.7 ft |
| 6 AWG | 36.7 ft | 18.3 ft | 7.3 ft |
| 4 AWG | 58.4 ft | 29.2 ft | 11.7 ft |
| 2 AWG | 92.8 ft | 46.4 ft | 18.6 ft |
| 1/0 AWG | 147.5 ft | 73.8 ft | 29.5 ft |
A 12 V fridge drawing 10 A, 15 feet from the battery, needs 8 AWG even though 14 AWG has the ampacity. That is why RV and van wiring often looks oversized next to house wiring. For solar arrays, the solar cable size calculator applies the same check with PV-specific current rules.
Copper or aluminum?
The last column of the main chart shows the trade. Aluminum carries roughly 78 to 80% as much current as copper of the same size, so a 100 A feeder needs 1 AWG aluminum instead of 3 AWG copper. In exchange it costs much less per foot at large sizes and weighs less. Aluminum makes sense for feeders, service entrance cable and long runs to outbuildings. Copper is the norm for branch circuits of 30 A and below. Our aluminum wire ampacity chart covers every aluminum size, the 83% dwelling service rule and termination practice.
When a job has several variables at once, such as distance, load, temperature and material, the wire size calculator checks ampacity and voltage drop together and returns the larger of the two answers.
Frequently asked questions
What gauge wire do I need for 20 amps?
12 AWG copper is the minimum for a 20 A circuit, including 12/2 NM cable. Use 10 AWG if the run is long enough to push voltage drop past 3%, which for a fully loaded 120 V circuit starts at roughly 47 feet one way.
Does a wire gauge amp chart apply to DC wiring?
Yes for heating, since a conductor warms the same way with AC or DC current. But in 12 V and 24 V systems, voltage drop almost always forces a larger wire than the ampacity chart suggests, so size low-voltage DC runs by distance first.
Why do some charts show much higher amps for the same gauge?
Charts labeled “chassis wiring” or “free air” describe single wires inside equipment with open air around them. They are not for building wire in walls, cables or conduit. For house wiring, use NEC Table 310.16 values.
How much bigger is each step in wire gauge?
Each AWG step changes cross-sectional area by about 26%, so every three gauge numbers the area roughly doubles and resistance halves. That is why going from 12 to 10 AWG cuts voltage drop by a bit more than a third.
Can I use the 90°C column for THHN wire?
Only as the starting point for derating. Breakers and panel lugs are usually rated 60°C or 75°C, and the circuit is limited by the lowest rating, so the final ampacity you use must come from that column.